The EFD system is a compact 482.6 mm (19″), 1 U early fire detection system with active smoke extraction system.
- Article number:
- DK 7338.221
- Product description
- The EFD III early fire detection system includes the smoke extraction system in a 482.6 mm (19″) subrack with just 1 U. An integral fan continuously extracts air from the area being protected via a system of pipes. The air drawn in passes two fire detectors. If smoke is detected, the highly sensitive detector will emit a pre-alarm, while the second detector will activate the main alarm. The fire detectors are permanently monitored for correct functioning by the evaluation and control electronics on the control card.
- Benefits
- Early fire detection
- 482.6 mm (19″) rack mount with just 1 U
- Tested by VdS Schadenverhütung GmbH
- CAN bus interface to the CMC III monitoring system
- Floating relay outputs (pre-alarm/main alarm/collective fault)
- Material
- Sheet steel
- Colour
- Enclosure: RAL 7035
Front: RAL 9005 - Interfaces
- 4 x/3 x relay outputs for alarms and faults (terminals/RJ12 jacks)
- 1 x/1 x input for door contact switch (terminal/RJ12 jack)
- 2 x CAN connections for master-slave networking
- 3 x connection (external alarm/manual call point/tank and fill level)
- 1 x voltage output for DET-AC slave III (24 V DC max. 500 mA)
- 1 x USB
- 2 x CAN bus interfaces to CMC III (max. 16 on PU/4 on PU Compact)
- Uninterruptible mains electricity operation
- approx. 4 h
- Note
- This system is designed solely for use in closed, non-accessible enclosure systems.
- Display
- Plain-language display with 6 LEDs
- Sensors
- Optical smoke detector (sensitivity: approx. 3.5%/m light obscuration)
- Optical smoke detector HS (sensitivity: approx. 0.25%/m light obscuration)
- Dimensions
- Width: 482.6 mm
Height: 44 mm
Depth: 490 mm - Operating temperature range
- 10 °C…40 °C
- Storage temperature range
- -20 °C…65 °C
- Storage temperature range of batteries
- -15 °C…40 °C
- Relative humidity (non-condensing)
- 96 %
- Rated operating voltage
- 100 V – 240 V, 1~, 50 Hz/60 Hz
- Air flow monitoring
- approx. ±10% of total airflow
- Packs of
- 1 pc(s).
- Weight/pack
- 15 kg
- PCF/PU (Cradle-to-Gate)
- 57.2 kg CO2 eq (Cat B)
- Note on the PCF class
- Category B: PCF value (cradle-to-gate) approximated based on product weight and self-declared
- Customs tariff number
- 85311095
- EAN
- 4028177699328
- ETIM 7.0
- EC002685
- ECLASS 8.0
- 40040104
- Product description
- DK EFD III, Early fire detection including smoke extraction system, Designed solely for use in closed, non-accessible enclosure systems, 482.6 mm (19″) rack mount, 1 U