Compact fire alarm and active extinguisher system with smoke extraction system, built into one height unit for use in security safes and closed server racks.
- Article number:
- DK 7338.121
- Product description
- The active extinguisher system includes the smoke extraction system and the extinguisher unit. The smoke extraction system is identical to the smoke extraction system in the EFD III. The extinguishing process begins automatically when a main alarm is activated. For the extinguishing process, the tank is pressurised via a propellant cartridge. The extinguisher gas Novec™ 1230 evaporates at the extinguisher nozzle and is distributed in the server enclosure.
- Benefits
- Early fire detection
- Automatic extinguishing
- Innovative extinguisher Novec™ 1230: eco-friendly, non-critical for IT components, non-conductive
- 482.6 mm (19″) rack mount with just 1 U
- Tested by VdS Schadenverhütung GmbH
- CAN bus interface to the CMC III monitoring system
- Floating relay outputs (pre-alarm/main alarm/collective fault)
- Technical specifications
- Extinguisher is emitted via a propellant cartridge, with integral electrical activation unit
- Integral extinguisher monitoring (indication of >15% loss)
- Material
- Sheet steel
- Colour
- Enclosure: RAL 7035
Front: RAL 9005 - Extinguisher gas
- Type: Novec™ 1230
Fill volume: 1.8 l - Tank
- Material: Aluminium
Volume: 2 l - Interfaces
- 4 x/3 x relay outputs for alarms and faults (terminals/RJ12 jacks)
- 1 x/1 x input for door contact switch (terminal/RJ12 jack)
- 2 x CAN connections for master-slave networking
- 2 x connection (external alarm/manual triggering device)
- 1 x voltage output for DET-AC slave III (24 V DC max. 500 mA)
- 1 x USB
- 2 x CAN bus interfaces to CMC III (max. 16 on PU/4 on PU Compact)
- Uninterruptible mains electricity operation
- approx. 4 h
- Note
- This system is designed solely for use in closed, non-accessible enclosure systems with a maximum volume of 2.8 m³.
- Display
- Plain-language display with 6 LEDs
- Sensors
- Optical smoke detector (sensitivity: approx. 3.5%/m light obscuration)
- Optical smoke detector HS (sensitivity: approx. 0.25%/m light obscuration)
- Dimensions
- Width: 482.6 mm
Height: 44 mm
Depth: 660 mm - Operating temperature range
- 10 °C…40 °C
- Storage temperature range
- -20 °C…65 °C
- Storage temperature range of batteries
- -15 °C…40 °C
- Relative humidity (non-condensing)
- 96 %
- Rated operating voltage
- 100 V – 240 V, 1~, 50 Hz/60 Hz
- Air flow monitoring
- approx. ±10% of total airflow
- Packs of
- 1 pc(s).
- Weight/pack
- 21.5 kg
- PCF/PU (Cradle-to-Gate)
- 81.9 kg CO2 eq (Cat B)
- Note on the PCF class
- Category B: PCF value (cradle-to-gate) approximated based on product weight and self-declared
- Customs tariff number
- 84241000
- EAN
- 4028177699311
- ETIM 7.0
- EC002685
- ECLASS 8.0
- 40040104
- Product description
- DET-AC III Master, fire alarm and extinguisher system, active smoke extraction system, early fire detection, automatic extinguishing.